山特3C20KS在线式UPS电源山特20KVA
1.保管时请注意温度不要超过-20℃~+40℃范围
2.保管电池时必须使电池在完全充电状态下进行保管。由于在运输途中或保存期内因自放电会损失一部分容量,使用时请补充电。
3.长期保管时,为弥补保管期间的自放电, 请进行补充电。在超过40C条件下保管时,对电池寿命有很坏影响,请避免!
4.请在干燥低温,通风良好的地方进行保管。5.如在保管或转移过程中电池包装不慎被水淋湿,应立即除掉包装纸箱,以避免被水打湿的纸箱成为导体造成电池放电或烧坏正极端子。
Installation notice
When installing batteries,observe the following:
1.1 Do not install batteries ina sealed space or near a fire; otherwise, there is a risk ofexplosion and fire.
1.2 Do not cover the batterywith things that may cause static electricity, because staticelectricity sometimes causes an explosion.
1.3 Do not install batteries inplaces where water is likely to enter; otherwise, electric shockand fire may occur.
1.4 Do not install batteries inan environment exceeding -40 °C to 60 °C.
1.5 Do not use the battery in aplace with dust, otherwise it may cause a short circuit of thebattery.
1.6 When putting the batteryinto the box, pay attention to the air circulation. 222.jpg timg(22).jpg
1.7 Do not have sticky orlabeled objects pressing the upper cover, because there is anexhaust valve under the upper cover, the gas generated in thebattery will not escape.
1.8 Number of parallelconnections - When floating charging, the plug-in terminal batterycan only be associated with three columns, and the bolt-fastenedterminals have no special restrictions, but the number of parallelconnections is small and the reliability is increased. Whenconnecting in parallel, it is necessary to consider that the wiringconductor and contact resistance between the columns are the same.In order to keep the charge-discharge battery in each columnbalanced, the actual use should not exceed threecolumns.
1.9 When using batteries withdifferent capacities, new and old, and different manufacturers, thebattery and the machine may be damaged due to their differentcharacteristic values, please avoid using them.
山特3C20KS在线式UPS电源浮充充电时,请用充电电压2.275V/单格(20℃时的设定值),进行定电压充电或0.002CA以下的电流进行定电流充电。温度有0C以下或40C以上时,有必要对充电电压进行修正,以20C为起点每变化一度,单格电压变化-3mv。2、循环充电时,充电电压以2.40-2.50V/单格(20℃时的设定值),进行定电压电压充电。温度在5C以下或35℃以上进行充电时,以20℃为起点,每变化一度充电电压调整-4mv/单格。
充电初期电流控制在0.25CA以下。
充电量设为放电量的100-120%,但环境温度在5C以下时,设为120-130%。
温度越低(5C以下)充电结束时间越长,温度越高(35C以上)越容易发生过充电,特别是在循环使用时,在5C~30C内进行充电较好。
为防止过充电尽量安装充电计时器,或自动转换成涓流式充电方式。
充电时电池温度要控制在-15C~+40C的范围内。
关于放电
放电时请将电池温度控制在-15℃- +50℃的范围内。
连续放电电流请控制在3CA以下(H控制在6CA以下)。
放电终止电压依电流的大小而变化,大体如下所述。注意放时,电压不得低于下述电压。
放电以后请迅速充电。如不小心过放电之后也请立即充电。
山特3C20KS在线式UPS电源山特20KVA